logo
Xian LongWell Machinery Equipment Co., LTD
製品
製品
ホーム > 製品 > Drill Rig Accessories > ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking

ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking

製品詳細

起源の場所: 中国

ブランド名: XD

証明: ISO9001

モデル番号: ZW32-12

支払及び船積みの言葉

最小注文数量: 1

支払条件: T/T

お問い合わせ
ハイライト:

12kV Rated Voltage Vacuum Circuit Breaker

,

Outdoor High Voltage Circuit Breaker

,

Capacitive Power Taking Circuit Breaker

モデル:
ZW32-12
定格電圧:
12KV
定格電流:
630、1250 a
定格周波数:
50 Hz
モデル:
ZW32-12
定格電圧:
12KV
定格電流:
630、1250 a
定格周波数:
50 Hz
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking
ZW32-12 Deep Fusion Outdoor High Voltage Vacuum Circuit Breaker Series (Capacitive Power Taking)
The ZW32-12 Deep Fusion Outdoor High Voltage Vacuum Circuit Breaker Series (Capacitive Power Taking) can be integrated with box-type cover low-power distribution terminals to accommodate various user demand modes. The switch body can output power supply side voltage signals, load side voltage signals, zero sequence voltage signals (8u), current signals, and zero sequence current signals (4i) according to distribution network requirements. The voltage and current sensor accuracy meets line measurement specifications.
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking 0
Product Overview
Three-phase AC 50Hz outdoor high-voltage switchgear designed for 10kV electrical power systems in rural and urban power grids. Used for opening and closing load current, overload current, and short circuit current in various applications.
Available Standards
  • GB/T 1984-2014 High-voltage alternating-current circuit-breakers
  • GB/T 11022-2011 Common specifications for high-voltage switchgear and controlgear standards
  • DL/T 402-2016 High-voltage alternating-current circuit-breakers
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking 1
Product Parameters
No. Parameter Name Unit Value
1 Rated voltage kV 12
2 Rated current A 630, 1250
3 Rated frequency Hz 50
4 Rated insulation level Power frequency withstand voltage for 1 minute:
Dry test: Phases-phase voltage, Voltage to ground: 42 Break voltage: 48 kV
Wet test: 34 kV
Lightning impulse withstand voltage (peak):
Phases-phase voltage, Voltage to the ground: 75 Break voltage: 85
5 Rated circuit-breaker breaking current kA 20 | 25
6 Rated short-circuit making current (peak) kA 50 | 63
7 Rated peak withstand current kA 50 | 63
8 4s thermal stability current kA 20 | 25
9 Rated operating sequence O-0.3s-CO-180s-CO
10 Closing time ms ≤50
11 Opening time ms ≤50
12 Rated short-circuit breaking current ON/OFF times Times 30
13 Mechanical life 10000
14 Control circuit and auxiliary circuit, power frequency withstand voltage for 1 minute V 2000
15 Rated operating voltage and auxiliary voltage AC/DC220, DC110/48/24
16 Rated current of overcurrent trip coil A 5
17 Allowable wear thickness of dynamic and static contacts in arc extinguish chamber mm 3
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking 2
Working Environment Conditions
  • Ambient air temperature: Max. temperature: +45℃; Min. temperature: -40℃; Max. daily temperature difference: 25K
  • Relative humidity: Daily mean ≤ 95%, Monthly mean ≤ 90%
  • Altitude: ≤ 2000m
  • Wind: ≤ 35m/s (equivalent to air pressure 700Pa)
  • Pollution grade: Grade IV
  • Radial thickness of ice: 10mm
  • Earthquake resistance: Horizontal acceleration: 0.3g/s²; Vertical acceleration: 0.2g/s²
  • Installed in locations free of fire, explosion, chemical corrosion and frequent severe vibration
  • Contact manufacturer for customizations outside normal working conditions
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking 3
Technical Features
  • Comprises three-phase pole, spring operating mechanism, drive system, conducting loop, control unit and housing (carbon steel spray or stainless steel). Features three-phase pole design with miniaturization, full-closed structure and excellent sealing, ideal for cold and wet regions
  • Efficient spring operating mechanism (manual or electric) with low-power energy-storage motor and minimal energy consumption. Sealed mechanism box prevents rust and ensures reliable operation
  • Pole construction uses imported epoxy resin with silicone rubber coating for high temperature, low temperature, UV and aging resistance
  • External two-phase or three-phase protective current transformer enables overcurrent protection, fault current quick-break protection with inrush current, and adjustable protection delay time
  • Interphase protection CT and zero-sequence CT integrated structure with intelligent controller enables parameter setting, single-phase grounding protection, three-section protection, reclosing, and fault memory. External power supply PT provides operating power
  • Controller includes communication module for data upload, fault feedback and "four-remote" functions to achieve distribution network automation
  • Optional isolating knife switch (single or dual sides) with three-phase linkage creates clear isolating distance. Mechanical anti-misoperation interlock ensures safe operation between main switch and isolating switch
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker with 12kV Rated Voltage and Capacitive Power Taking 4